(One intermediate revision by one user not shown) |
Line 1: |
Line 1: |
| {{Biogas Project Database | | {{Biogas Project Database |
− | |BSP Project Name=Thermo-technical retrofitting of public buildings | + | |BSP Project Name=Thermo-technical retrofitting of a health center |
| |BSP Project Desc=Within the project 'Energy efficiency in the grid-connected energy supply' implemented by GIZ on behalf of the German federal Ministry for Economic Cooperation and Development (BMZ) and Swiss Development Cooperation (SDC) sixteen (16) have been retrofitted. This one of these buildings. | | |BSP Project Desc=Within the project 'Energy efficiency in the grid-connected energy supply' implemented by GIZ on behalf of the German federal Ministry for Economic Cooperation and Development (BMZ) and Swiss Development Cooperation (SDC) sixteen (16) have been retrofitted. This one of these buildings. |
− | |BSP Project Status=Planned | + | |BSP Project Budget=174,100,000.00 MNT |
− | |BSP Province=46.862496, 103.846656 | + | |BSP Project Status=Completed |
| + | |BSP Project Start=01.07.2015 |
| + | |BSP Project Type=other |
| + | |BSP Project End=07.09.2015 |
| + | |BSP Project Picture=Khovd Duut.png |
| + | |BSP Province Name=Khovd |
| + | |BSP Province=47.520961, 91.630275 |
| + | |BSP Organization=GIZ |
| + | |BSP Tag Building=Building improvement |
| + | |BSP Tag Efficient=Efficient use of resources |
| }} | | }} |
| + | |
| + | ==== Building data and geometry<br/> ==== |
| + | |
| + | *Construction year: 1975<br/> |
| + | *Cross volume: 1,909.1 m³<br/> |
| + | *Thermal envelope: 1,489.9 m²<br/> |
| + | *Net volume: 1,261.2 m³<br/> |
| + | *Net floor area: 441.3 m²<br/> |
| + | |
| + | ==== Implemented measures:<br/> ==== |
| + | |
| + | *Roof insulation with 20cm EPS- hard foam and waterproofing<br/> |
| + | *Wall insulation with 15cm EPS- hard foam<br/> |
| + | *New windows with 5-chamber plastic frame and double glazing<br/> |
| + | *New exterior doors |
| + | |
| + | Contracting company: '''Buyantiin Borgio LLC''' |
| + | |
| + | ==== Energy consumption<br/> ==== |
| + | |
| + | *Before: 473 kWh/(m2 a) {calculated}<br/> |
| + | *After: 242 kWh /(m2 a) {metred}<br/> |
| + | *Energy saving per year: 101,871 kWh<br/> |
| + | *Coal equivalent saving: 25,029 kg / 25 t<br/> |
| + | *CO<sub>2</sub> emission savings per year: 68.8 t CO<sub>2 </sub>{Estimated} |